QuickHMI is compatible with:
- Siemens S7 controllers via put/get access (200, 300, 400, 1200, 1500, ET200SP series as well as SoftPLC WinAC RTX), Logo!0BA7 and Logo!0BA8 as well as CPUs from other manufacturers (e.g. VIPA 100V/200V/300V/300S)
- Siemens S7 controllers via symbolic access (1200, 1500, ET200 series) 1*)
- OPC UA interface
- TWINCAT2 from version 2.1 and TWINCAT3 2*)
- MODBUS TCP, RTU, RTU via TCP or ASCCI
- Allen-Bradley “Control Logix” or “Compact Logix” controllers via Ethernet/IP protocol
- KNX/EIB
- MQTT protocol
- Various SQL databases using JDBC
- Files from the file system with the file system data source
- InfluxDB
Native migration of additional protocols is planned.
*1) Certain requirements must be met for symbolic access:
- The controller software must have been created with at least TIA version 17.
- If software components were created with an earlier version, they must be recompiled and transferred with TIA version 17 or higher. The same applies to the hardware configuration of the PLC.
- At least the following firmware versions are required:
- S7-1200 series with firmware versions V4.5, tested and validated up to version 4.6
- S7-1500 series from firmware version V2.9 , tested and validated up to version 3.1
- S7-ET200SP series from firmware version V2.9 , tested and validated up to version 3.1
- If a password has been assigned at controller level, you must have it. The password can be transferred up to firmware version 3.0 (1500 and ET200 series) or 4.6 (S7-1200 series). For higher firmware versions, the login mechanism has changed on the PLC side; the new “Anonymous” user must be configured and enabled in the PLC.
*2) TwinCat data sources are not executable under Linux. If these are to be executable under Linux, the use of OPC UA data sources is recommended.