QuickHMI is compatible with:
- Siemens S7 controllers via put/get access (200, 300, 400, 1200, 1500, ET200SP series as well as SoftPLC WinAC RTX), Logo!0BA7 and Logo!0BA8 as well as CPUs from other manufacturers (e.g. VIPA 100V/200V/300V/300S)
- Siemens S7 controllers via symbolic legacy access (1200, 1500, ET200 series) 1*)
- Siemens S7 controllers via symbolic TLS access (1200, 1500, ET200 series) 2*)
- OPC UA interface
- TWINCAT2 from version 2.1 and TWINCAT3
- MODBUS TCP, RTU, RTU via TCP or ASCCI
- Allen-Bradley "Control Logix" or "Compact Logix" controllers via Ethernet/IP protocol *3)
- BACnet *4
- KNX/EIB
- MQTT protocol
- Various SQL databases using JDBC
- Files from the file system with the file system data source
- InfluxDB
- Java universal data source (create your own data source with the Java API)
- Native migration of further protocols is planned
*1 Legacy access must be enabled for the connection.
*2)Certain requirements must be met for symbolic access via TLS:
- The controller software must have been created with at least TIA version 17.
- If software components were created with an earlier version, they must be recompiled and transferred with TIA version 17 or higher. The same applies to the hardware configuration of the PLC.
- At least the following firmware versions are required:
- S7-1200 series with firmware versions V4.5, tested and released up to version 4.7
- S7-1500 series from firmware version V2.9, tested and released up to version 4.0
- S7-ET200SP series from firmware version V2.9, tested and released up to version 4.0
Note: When using the older legacy access for communication with a simulated controller, no password must be assigned. This restriction does not apply when using dedicated hardware controllers.
*3 ARM-based systems are not supported.
*4 BACnet IP4 Revision 19

